CT (external current sensor) 100A MP-FEC100

MP-FEC100 - CT (external current sensor) 100A

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

Software

  • CE Marking
  • CSA

Specifications

Model

MP-FEC100

Primary side rated current (In)

100 A

Overcurrent withstand capability

1.2 times the primary side rated current (can be continuous)

Maximum wire diameter that can be installed

ø24

Installation method

Clamp type (split core)

Ratio error to current load

±2.0% of RD (20% ≤ In ≤ 100%)

Phase difference for current load

±240’ (20% In) ±180’ (100% In)

Withstand voltage

2300 VAC for 1 minute (between core and output line)

Insulation resistance

500 VDC/100 MΩ or more (between core and output line)

Protection elements

Internal clamping element

Environmental resistance

Ambient temperature

-10 to +55°C (no freezing)

Relative humidity

35 to 85% RH (no condensation)

Material

Nylon

Weight

Approx. 300 g (with cable)