PROFINET Compatible Network Unit NU-PN1

NU-PN1 - PROFINET Compatible Network Unit

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD / CAE

360°view (3D PDF)

Software

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

NU-PN1

Name

PROFINET Compatible Network Unit

Compatible network

PROFINET I/O communication

Ethernet
Specifications

Compliant standards

IEEE802.3u (100BASE-TX)

Transmission rate

100 Mbps (100BASE-TX)

Transmission media

STP cable or Category 5 or higher UTP cable

Maximum cable length

100 m

Max. number of connection stages

2

PROFINET

Compatible functions

Cyclic communication (Data I/O communication)
Acyclic communication (Record data communication)

Number of connectable controllers

1

Update Time

2 to 512 ms

Version of GSDML

Version 2.3

Conformance class

Complies with conformance class A

Conformance test version

Complies with version 2.2.4

Applicable protocols

LLDP, DCP

Sensor connection

Connectable sensors

Sensors with N-bus support *1

Number of connectable units

16 units max.
(varies depending on the sensors to connect)

Power supply

Power received from the NU-PN1 via the sensor connector

Allowable passing current

Overall 1200 mA or less *2

Power during PoE power receiving

Supply voltage: 24V±10%, supply current: 360 mA or less *3*4

Power voltage

24 VDC ±10%, ripple (p-p) 10% or less (with power supply connector)
48 VDC (Max. 57 VDC) (During PoE power receiving)

Power consumption

1500 mW or less (at 24 V 60 mA max) *5

Environmental resistance

Pollution degree

2

Ambient temperature

-20 to 55°C (no freezing)

Relative humidity

35 to 85% RH (no condensation)

Vibration resistance

10 to 55 Hz compound amplitude 1.5 mm, 2 hours each in X, Y, Z directions

Material

Main unit case: Polycarbonate
Power supply connector: Polyamide (plug), PBT (socket)

Weight

Approx. 80 g

*1 "N-bus" is the name of KEYENCE's wiring-saving system for sensors.
*2 Indicates the current that can be supplied to the NU-PN1 and to the sensor units linked to the NU-PN1.
*3 Power which can be supplied to sensor when using the PoE power receiving function.
*4 Varies according to the working ambient temperature.
(-20 to 45°C: 360mA or less, 45 to 50°C: 260mA or less, 50 to 55°C: 140mA or less)
*5 Does not include power supplied to connected sensor.